Skip to content

Colocation

Planning Colocation Power: Amps, Volts, Watts and Headroom

Use measured input power and the agreed service limit rather than a power-supply label alone.

PowerCapacity208V
Reading time
2 min read
Published
Updated
Maintained by
EnderHost Team

Choose a colocation power allocation using the server’s measured input demand and the provider’s agreed limit. The wattage printed on a power supply describes its capacity, not the machine’s constant consumption. Idle draw alone is also insufficient for planning.

Keep the units distinct

For a single-phase load, volts multiplied by amps gives apparent power in volt-amperes. Real power in watts also depends on power factor. For example, 208 V at 1 A corresponds to 208 VA; it is not automatically a promise that every 208 W load is acceptable under a service agreement.

Information to collect
ItemWhy it matters
Input voltage rangeThe server must support the supplied power
Measured idle and busy demandWorkload changes can alter consumption
Startup and recovery behaviorBooting or rebuilding can differ from normal load
Power-supply and feed arrangementRedundancy depends on the complete power path
Agreed operating limitThe service allowance governs deployment

Build a representative power profile

  1. Use supported management telemetry or approved measurement equipment.
  2. Record idle demand and a representative busy workload.
  3. Include the drives, memory, accelerators and fans in the final configuration.
  4. Discuss peak behavior and the required operating margin with the provider.
  5. Confirm connectors, feed arrangements and any upgrade charges before shipping.

Two power supplies do not necessarily mean two independent feeds, and normal load sharing does not establish the draw after one supply or feed fails. Have the provider confirm the intended arrangement. Do not modify electrical equipment or bypass rated limits to make a configuration fit.

Recheck after hardware changes

Adding drives or an accelerator can invalidate the original estimate. Keep a power baseline with your equipment inventory and review it before an upgrade. If the configuration exceeds the agreed allocation, arrange a suitable service rather than relying on the fact that the server currently boots.

Use this with the shipping checklist and compare the location-specific options on the colocation page.

Sources and references

Hosting documentation. Publication and update dates reflect this edition.